Pick a motor (horsepower and voltage, or kilowatts) and get the NEMA size and the IEC AC-3 rating that cover it, using the published NEMA ICS 2, IEC 60947-4-1 and NEC 430.250 tables. Or start from a NEMA size or an IEC current and see the other side. Then browse real contactors in our catalog that meet the result, by their own published ratings. This compares standards and specs; it never claims one brand's part number equals another's.
How much of each brand's range carries these specs
The catalog matcher can only use values a listing actually publishes. This is the honest coverage, so a brand with few spec values is not mistaken for a brand with no matching product.
Brand
Contactors listed
With NEMA size
With current rating
With coil voltage
Allen-Bradley
4131
1669
739
1384
Siemens
2543
0
1094
937
Schneider Electric
1465
0
535
435
WEG
1210
0
193
382
BAOMAIN
694
0
0
0
Eaton
510
0
30
0
ABB
422
0
42
0
ABB Low Voltage
351
0
232
0
WEG Electric
242
0
217
0
Schneider
194
0
0
0
Reference tables
NEMA ICS 2 contactor sizes: continuous current and maximum three-phase horsepower
NEMA size
Continuous A
200 V hp
230 V hp
460 V hp
575 V hp
Size 00
9
1.5
1.5
2
2
Size 0
18
3
3
5
5
Size 1
27
7.5
7.5
10
10
Size 2
45
10
15
25
25
Size 3
90
25
30
50
50
Size 4
135
40
50
100
100
Size 5
270
75
100
200
200
Size 6
540
150
200
400
400
Size 7
810
—
300
600
600
Size 8
1215
—
450
900
900
Size 9
2250
—
800
1600
1600
208 V motors use the 200 V column. A dash means the size is not rated at that voltage.
IEC AC-3 operational currents and the 400 V motor rating they suit
AC-3 current (A)
Motor at 400 V (kW)
6
2.2
7
3
9
4
12
5.5
18
7.5
25
11
32
15
38
18.5
40
18.5
50
22
65
30
80
37
95
45
115
55
150
75
185
90
225
110
265
132
330
160
400
200
500
250
630
315
800
400
NEC 430.250 full-load current of three-phase induction motors (amps)
Horsepower
200 V
208 V
230 V
460 V
575 V
0.5 hp
2.5
2.4
2.2
1.1
0.9
0.75 hp
3.7
3.5
3.2
1.6
1.3
1 hp
4.8
4.6
4.2
2.1
1.7
1.5 hp
6.9
6.6
6
3
2.4
2 hp
7.8
7.5
6.8
3.4
2.7
3 hp
11
10.6
9.6
4.8
3.9
5 hp
17.5
16.7
15.2
7.6
6.1
7.5 hp
25.3
24.2
22
11
9
10 hp
32.2
30.8
28
14
11
15 hp
48.3
46.2
42
21
17
20 hp
62.1
59.4
54
27
22
25 hp
78.2
74.8
68
34
27
30 hp
92
88
80
40
32
40 hp
120
114
104
52
41
50 hp
150
143
130
65
52
60 hp
177
169
154
77
62
75 hp
221
211
192
96
77
100 hp
285
273
248
124
99
125 hp
359
343
312
156
125
150 hp
414
396
360
180
144
200 hp
552
528
480
240
192
Canadian installations follow CEC Table 44, whose values can differ slightly. Always confirm against the motor nameplate.
Frequently asked questions
What is the difference between a NEMA and an IEC contactor?
NEMA contactors are sized in standard steps (00 to 9), each rated for a maximum motor horsepower at each voltage and built with generous margins. IEC contactors are rated by an AC-3 operating current, and the motor kW that current suits at 400 V, in finer steps and are usually more compact. Both switch the same motors; the rating basis differs, which is why the two cannot be compared by size number alone.
How do I size a contactor for a motor?
Start from the motor's full-load current on the nameplate, or NEC Table 430.250 when the nameplate is not available. For an IEC contactor choose an AC-3 rating at or above that current at your voltage. For a NEMA contactor choose the smallest size whose horsepower rating at your voltage covers the motor. Then size up for jogging, plugging or frequent starting (AC-4 duty), high ambient temperature or altitude, and check the overload relay range separately.
Is a NEMA size 1 the same as a 32 A IEC contactor?
Not exactly. A NEMA size 1 is rated 27 A continuous and 10 hp at 460 V. The smallest standard IEC AC-3 rating above 27 A is 32 A, which is rated for a 15 kW motor at 400 V. The numbers are close but the rating bases differ, so the manufacturer's own NEMA-to-IEC conversion chart decides whether a swap is acceptable, including overload relay, mounting and auxiliary contact differences.
Does this tool say a Schneider contactor equals an Allen-Bradley contactor?
No. Catalog numbers are not built on a shared cross-brand standard, so a claimed equivalence would be a guess. This tool compares the published standards (NEMA size and IEC AC-3 current) and lists real contactors from our catalog by their own published specs so you can compare them yourself against the datasheet.
Why do I see few Siemens or Schneider contactors in the matches?
Matches come from published spec fields in our catalog: current rating, NEMA size and control voltage. Allen-Bradley, WEG and ABB Low Voltage carry these for many of their contactors. Siemens and Schneider now carry the AC-3 current rating and coil voltage for a large share of their contactors, read from each manufacturer's own published description, but not all of them, so some listed contactors still do not appear in the match lists. Not appearing is not a statement that no match exists. Send us the part number or the motor details and our order desk will source it.
Do these tables apply in Canada?
The horsepower and current tables follow the NEC and NEMA. Canadian installations use CEC Table 44 for motor full-load current, whose values can differ slightly, and the local authority or the manufacturer's Canadian datasheet governs. Treat the result as a starting point and confirm it against the motor nameplate.