Conduit Fill Calculator

Pick the conduit type and trade size, then add up to four groups of conductors, and get the fill percent against the NEC limit, whether it passes, and the smallest trade size that does. Or choose one wire size and get the most conductors that fit. Uses NEC Chapter 9 Tables 1, 4 and 5 for THHN and XHHW.

Used with: Check the fill of a conduit; Maximum conductors of one size
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit
Used with: Check the fill of a conduit

Worked example

These are example values. Change any entry above and press Calculate to run your own numbers.

Conduit EMT (electrical metallic tubing), 3/4"
Conductors 4 × 12 AWG (0.0133 in² each); 2 × 10 AWG (0.0211 in² each) (THHN / THWN / THWN-2)
Number of conductors 6
Total conductor area 0.0954 in²
Conduit internal area (100%) 0.533 in²
Fill limit for 6 conductors 40% = 0.213 in²
Your fill 17.9 %
Result Within the NEC fill limit Area to spare: 0.1176 in²
Smallest EMT size that passes 1/2" at this fill limit

Include every conductor in the conduit, equipment grounding conductors too. Bare conductors use NEC Table 8, which this tool does not cover.

Figures are from NFPA 70 (NEC) 2017 Edition, Chapter 9, Tables 1, 4 and 5. Confirm against the edition your authority adopts. This tool does not cover derating, bends, nipples, conduit bodies or other code rules, and is not a substitute for the code or a qualified electrician.

How it works

The National Electrical Code limits how much of a conduit's cross-section the conductors may fill, so they can be pulled in and can shed heat. The limit is 53% for one conductor, 31% for two and 40% for three or more. The calculator adds up the area of every conductor from Chapter 9 Table 5 and compares it with the matching share of the conduit area from Table 4.

The formulas

  • Fill % = total conductor area ÷ conduit internal area × 100
  • Limit: 1 conductor 53%, 2 conductors 31%, 3 or more 40% (NEC Chapter 9, Table 1)
  • Most conductors of one size = 40% of the conduit area ÷ the area of one conductor
  • Note 7: for same-size conductors, a result with a fraction of 0.8 or more rounds up to the next whole conductor
  • Conductor and conduit areas come from NEC Chapter 9, Tables 4 and 5

Reference tables

Conduit fill chart: most THHN conductors in EMT (40% fill)
Wire size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 3 1/2" 4"
14 AWG 12 22 35 61 84 138 241 364 476 608
12 AWG 9 16 26 45 61 101 176 266 347 443
10 AWG 5 10 16 28 38 63 111 167 219 279
8 AWG 3 6 9 16 22 36 64 96 126 161
6 AWG 1 4 7 12 16 26 46 69 91 116
4 AWG 1 2 4 7 10 16 28 43 56 71
3 AWG 1 1 3 6 8 13 24 36 47 60
2 AWG 1 1 3 5 7 11 20 30 40 51
1 AWG 1 1 1 4 5 8 15 22 29 37
1/0 AWG 0 1 1 3 4 7 12 19 25 32
2/0 AWG 0 1 1 2 3 6 10 16 20 26
3/0 AWG 0 1 1 1 3 5 8 13 17 22
4/0 AWG 0 0 1 1 1 4 7 11 14 18

Three or more same-size THHN/THWN conductors in EMT, NEC Chapter 9 Tables 4 and 5 (2017 edition), with the Note 7 round-up. Charts for the 53% and 31% single and two-conductor limits, and for other conduit types and XHHW, are on the calculator above. Confirm against the edition your authority adopts.

EMT dimensions and fill areas (NEC Chapter 9, Table 4)
Trade sizeInternal diameter (in)Total area (in²)53% (in²)40% (in²)31% (in²)
1/2" 0.622 0.304 0.161 0.122 0.094
3/4" 0.824 0.533 0.283 0.213 0.165
1" 1.049 0.864 0.458 0.346 0.268
1 1/4" 1.38 1.496 0.793 0.598 0.464
1 1/2" 1.61 2.036 1.079 0.814 0.631
2" 2.067 3.356 1.778 1.342 1.04
2 1/2" 2.731 5.858 3.105 2.343 1.816
3" 3.356 8.846 4.688 3.538 2.742
3 1/2" 3.834 11.55 6.119 4.618 3.579
4" 4.334 14.75 7.819 5.901 4.573
Conductor areas, THHN/THWN and XHHW (NEC Chapter 9, Table 5)
SizeTHHN/THWN (in²)XHHW (in²)
14 AWG 0.0097 0.0139
12 AWG 0.0133 0.0181
10 AWG 0.0211 0.0243
8 AWG 0.0366 0.0437
6 AWG 0.0507 0.059
4 AWG 0.0824 0.0814
3 AWG 0.0973 0.0962
2 AWG 0.1158 0.1146
1 AWG 0.1562 0.1534
1/0 AWG 0.1855 0.1825
2/0 AWG 0.2223 0.219
3/0 AWG 0.2679 0.2642
4/0 AWG 0.3237 0.3197
250 kcmil 0.397 0.3904
300 kcmil 0.4608 0.4536
350 kcmil 0.5242 0.5166
400 kcmil 0.5863 0.5782
500 kcmil 0.7073 0.6984
600 kcmil 0.8676 0.8709
700 kcmil 0.9887 0.9923
750 kcmil 1.05 1.053
800 kcmil 1.109 1.112
900 kcmil 1.231 1.235
1000 kcmil 1.348 1.352

Frequently asked questions

How many 12 AWG wires fit in a 3/4 inch EMT conduit?

Sixteen THHN conductors of 12 AWG fit in 3/4 inch EMT at the 40% limit. In 1/2 inch EMT the limit is nine, and in 1 inch EMT it is 26. XHHW insulation is a little bulkier, so the same conduit holds fewer.

What is the NEC conduit fill limit?

NEC Chapter 9, Table 1 allows 53% of the conduit area for one conductor, 31% for two, and 40% for three or more. These limits assume a straight run and ordinary conditions. Other rules, such as those for nipples, lead-sheathed cable and some raceway types, set different figures.

What is Note 7 and why does the answer sometimes round up?

Note 7 to the Chapter 9 tables says that when all the conductors are the same size and the number that fits works out at 0.8 or more above a whole number, you may round up. Six 8 AWG THHN conductors in 3/4 inch EMT is an example: the arithmetic gives 5.82 and the note permits six. The calculator applies this only for a single group of one size.

Do I count the grounding conductor?

Yes. Chapter 9 Note 3 requires equipment grounding and bonding conductors to be included when you calculate fill. Add them as another group of conductors. Bare conductors use Table 8 areas, which this calculator does not cover.

Why does this chart sometimes differ by one from other charts?

For a single conductor or a pair, a few published conduit fill charts round the result differently from the strict Table 1 limit. This calculator uses the printed Table 1 percentages, so where the 53% or 31% column governs it can show a lower count. For three or more conductors, the common case, the figures match the usual charts.

Does this cover conduit longer or shorter than a normal run?

No. A conduit nipple of 24 inches or less may be filled to 60% under Chapter 9 Note 4, and this tool does not apply that. It also does not cover derating for more than three current-carrying conductors, pulling tension, bends, or conduit bodies. Use the code and a qualified electrician for those.