Beckhoff EL3602 — EtherCAT Terminals
The EL3602 analog input terminal handles signals in the ranges ±10 V, ±5 V, ±2.5 V and ±1.25 V. The voltage is digitized to a resolution of 24 bits, and is transmitted, electrically isolated, to the higher-level automation device. The input channels of
| Approvals/markings | CE, CCC, UL, ATEX, IECEx |
|---|---|
| Common mode voltage UCM | max. 35 V |
| Conversion time | 20 ms default setting, 1…400 ms configurable |
| Crosstalk attenuation | > 60 dB |
| Current consumption E-bus | typ. 190 mA |
| Current consumption power contacts | – |
| Distributed clock accuracy | – |
| Distributed clocks | – |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
| Input filter cut-off frequency | 3 kHz |
| Input signal bandwidth | – |
| Internal resistance | > 200 kΩ |
| Measurement error/uncertainty | < ±0.01% at 25°C, 50 Hz filter (relative to full scale value) |
| Number of inputs | 2 (differential) |
| Operating Temperature | -25…+60°C |
| Oversampling factor | – |
| Pluggable wiring level | for all ESxxxx terminals |
| Power Supply | via the E-bus |
| Protect. rating/installation pos. | IP20/variable |
| Relative Humidity | 95%, no condensation |
| Resolution | 24 bit (incl. sign) |
| Signal voltage | -10…+10 V, -5…+5 V, -2.5…+2.5 V, -1.25…+1.25 V (parameterizable) |
| Special Features | various filter times, limit value monitoring, high precision |
| Storage Temperature | -40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Weight | approx. 60 g |
Frequently Asked Questions
How do I get pricing for EL3602?
KKM Solutions is a quote-based industrial supplier, so prices are not listed online. Send the quote form on this page with your quantity, or email orderdesk@kkmsolutions.com, and our order desk will reply with pricing and availability within 1 business day.
Who manufactures the EL3602?
EL3602 is a Beckhoff part. KKM Solutions sources Beckhoff components to the exact manufacturer specification and cross-checks every order against manufacturer part data before it ships.
What are the key specifications of EL3602?
Key specifications include Approvals/markings: CE, CCC, UL, ATEX, IECEx; Common mode voltage UCM: max. 35 V; Conversion time: 20 ms default setting, 1…400 ms configurable; Crosstalk attenuation: > 60 dB. The full specification table on this page lists every published attribute for this part.
How quickly can EL3602 ship?
In-stock items are dispatched the same business day for orders placed by 3 PM; sourced and quoted items ship per the quoted lead time. KKM Solutions ships worldwide — to your site, warehouse, or freight forwarder.
Related Products
Beckhoff Beckhoff EtherCAT Terminal, 3-channel analog input, power measurement, 480…
Beckhoff Beckhoff EtherCAT Terminal, 2-channel analog input, current, 0…20 mA,…
Beckhoff Beckhoff EtherCAT Terminal, 3-channel analog input, power measurement, 500…
Beckhoff Beckhoff EtherCAT Terminal, 2-channel analog input, IEPE/accelerometer, 16 bit,…
Beckhoff Beckhoff EtherCAT Terminal, 1-channel analog input, measuring bridge, full…
Beckhoff
Industrial & MRO Parts