Overload Relay Trip Classes, and Why Yours Nuisance Trips

KKM Solutions · August 10, 2026

Overload relay trip class defines the time to trip at 600% of full-load current.

Overload Relay Trip Classes, and Why Yours Nuisance Trips — KKM Solutions technical article

Short answer

  • Trip class is the maximum time an overload relay allows 600% of full-load current to flow before breaking the control circuit, and a mismatch between that class and the motor's acceleration is the usual cause of nuisance trips.
  • Class 10 trips in 10 seconds, Class 20 in 20 seconds, and Class 30 in 30 seconds, so high-inertia fans that need longer than 10 seconds to accelerate require a Class 30 relay.
  • The adjustment dial should be set to the motor's nameplate FLA rather than breaker size, and phase-loss protection should be active because single-phasing can destroy a motor in minutes.

Your motor starter trips every time a high-inertia fan spins up, or you replace a burned-out motor and the new one fails six months later despite the overload seemingly being sized correctly. The root cause in both cases is usually a mismatch between the overload relay's trip class and the motor's actual thermal characteristics, combined with a misunderstanding of what the relay is actually protecting.

An overload relay does not protect the circuit from short circuits—that is the job of the fuses or circuit breaker upstream. Its sole purpose is to protect the motor's insulation from the cumulative thermal damage caused by currents slightly above full-load amperage (FLA). To do this effectively, it has to mimic the thermal behavior of the motor it protects. That mimicry is defined by the trip class.

What does overload relay trip class measure?

Trip class is the maximum time the relay will allow a current of 600% of the motor's FLA to flow before breaking the control circuit. This 600% benchmark represents the locked-rotor current (LRC) a standard motor draws when starting across the line. The class number dictates the time delay at that specific overload level.

  • Class 10: Trips in 10 seconds at 600% FLA. Used for general-purpose applications and submersible pumps, where rapid acceleration is expected and prolonged starting currents will quickly cook the windings.
  • Class 20: Trips in 20 seconds at 600% FLA. The standard for most industrial motors driving normal-inertia loads like centrifugal pumps and unloaded conveyors.
  • Class 30: Trips in 30 seconds at 600% FLA. Required for high-inertia loads like large fans, flywheels, or loaded screw conveyors that take a long time to reach operating speed.

If you put a Class 10 relay on a high-inertia fan, the relay will nuisance trip every time you start it. The motor is physically incapable of accelerating the mass in under 10 seconds, so it draws locked-rotor current for 12 or 15 seconds. The relay does exactly what it was designed to do: it sees a sustained 600% current and assumes the motor is burning up. Moving to a Class 30 relay gives the motor the time it needs to get past the acceleration phase. Conversely, putting a Class 30 on a fast-accelerating pump means the relay will tolerate a fault condition for far too long, allowing the motor to overheat before the protection kicks in.

Should the overload dial match FLA or breaker size?

A common field error is sizing the overload relay based on the upstream branch circuit protection. The circuit breaker is sized to handle the inrush current of the contactor and the fault capacity of the wiring. The overload relay is sized to the motor's continuous thermal limit. They are protecting entirely different things.

The adjustment dial on the relay must be set to the motor's nameplate FLA. If the motor has a service factor (SF) greater than 1.0—typically 1.15 on standard industrial motors—it means the motor can safely run continuously at that multiplied load under specific conditions. However, the overload relay should still generally be set at the base FLA. Setting the dial to FLA x 1.15 uses up the motor's thermal buffer and leaves no margin for voltage imbalances or ambient temperature spikes. If you find yourself needing to set the dial above FLA to stop nuisance tripping, you likely have the wrong trip class, a mechanical overload on the driven equipment, or a voltage imbalance causing the motor to draw more current.

When upgrading or replacing aging contactors and motor starters, it is critical to verify that the new overload relay's adjustment range actually encompasses the motor's FLA. An electronic overload with a wide adjustment range is often a better choice than a thermal unit with a narrow range, as it allows for flexibility in future motor swaps.

Why does single-phasing damage motors with thermal relays?

Standard bimetallic thermal overload relays rely on a heater element bending a bimetallic strip to trip the mechanism. If the motor draws more current, the heater gets hotter, and the strip bends further. But a basic three-element thermal relay measures current, not actual winding temperature. It assumes that if the current is normal, the motor is fine. That assumption fails catastrophically during a single-phase condition.

If one phase drops out while the motor is running, the motor does not stop. It continues to run on the two remaining phases. However, the current in those two phases can jump to 150% to 200% of normal to maintain the same shaft power. Worse, the distribution of that current inside the motor windings becomes highly uneven. The standard bimetallic relay sees an average current increase and trips eventually, but often not before localized hotspots in the stator windings have already exceeded the insulation's temperature limit.

Insulation life follows the 10°C halving rule: for every 10°C increase in operating temperature, the expected life of the insulation is cut in half. A motor running at 180°C will fail drastically faster than one running at 150°C. Single-phasing creates localized temperatures that can destroy a motor in minutes. This is why modern overload relays almost always include dedicated phase-loss and phase-imbalance protection.

Electronic overloads monitor each phase individually. If one phase drops to zero, the relay trips in milliseconds. If a phase imbalance occurs—say, a 5% voltage difference between phases—the relay calculates the resulting current imbalance and trips before the uneven current distribution damages the bearings or windings. A simple thermal element simply cannot provide this level of protection.

How do ambient heat and reset mode affect overload relays?

Bimetallic overload relays are subject to ambient temperature changes. If the starter panel is 40°C, the bimetallic strip is already partially expanded before any motor current flows. A standard relay in a hot control panel will trip at a lower current than its dial setting indicates. Conversely, in a refrigerated area, the relay will run cold and may not trip soon enough. If the relay and the motor are in significantly different ambient temperatures, you must use an ambient-compensated overload relay. These are designed to ignore the surrounding panel temperature and react strictly to the motor current.

Reset mode is another critical setting. Overload relays can be set to manual or automatic reset. Automatic reset should never be used on any equipment that can automatically restart. If a conveyor jams, the overload trips. The motor cools down, the bimetallic strip snaps back, and the control circuit closes. If the start contact is still engaged, the motor will suddenly restart without warning. If someone is clearing the jam by hand, the sudden restart causes severe injury.

Automatic reset is only acceptable on remote, inaccessible loads like submersible pumps where a manual reset is impractical, and only if the driven equipment cannot cause injury upon restarting. For all standard industrial machinery, the relay must be set to manual. The operator must physically press the reset button, which requires them to be at the starter panel and ideally verify the cause of the trip before restarting.

Why choose an electronic overload relay over a thermal one?

Electronic overload relays have largely replaced thermal bimetallic units in new installations, and for good reason. Instead of relying on a physical heater element, they use current transformers to measure the actual phase current, feed that into a microprocessor, and calculate the motor's thermal state using a mathematical model. This allows for extremely wide adjustment ranges—a single electronic overload might cover 5 to 25 amps, replacing three or four separate thermal units.

The mathematical model also accounts for the cooling time of the motor. If a thermal relay trips, it cools down and resets in a minute or two. The motor, however, takes much longer to physically cool. If the operator resets the thermal relay immediately and restarts the motor, the motor is still hot, but the relay thinks everything is fine. An electronic overload remembers the thermal state. If it trips, it will lock out the restart for a calculated cool-down period, preventing the motor from being subjected to repeated hot starts that would destroy the insulation.

Electronic units also offer trip class flexibility. Many allow you to select Class 5, 10, 20, or 30 via a dial or programming interface, meaning you can match the relay to the motor's exact acceleration curve without buying a different component. When sourcing replacements or upgrading legacy panels, looking at electronic options from established manufacturers like Schneider Electric or Sprecher & Schuh provides the flexibility to handle both standard and high-inertia applications with a single inventory unit.

Matching the trip class to the motor's acceleration profile, setting the dial to the nameplate FLA, and ensuring phase-loss protection is active will resolve the vast majority of nuisance tripping and premature motor failures. If you are troubleshooting a persistent issue or upgrading a legacy starter, the specific component cross-referencing can be sourced or quoted to match your exact motor specifications.

Related reading: what a contactor is and how to size one.

Related: Motor Protection Circuit Breakers (MPCB) Explained.

Need a quote on a specific part?

Our order desk replies within 1 business day. No account needed. Or email orderdesk@kkmsolutions.com.

Request a Quote

Frequently asked questions

What does overload relay trip class mean?

Trip class is the maximum time the relay allows a current of 600% of the motor's FLA to flow before breaking the control circuit. The 600% benchmark represents the locked-rotor current a standard motor draws when starting across the line. Class 10 trips in 10 seconds, Class 20 in 20 seconds, and Class 30 in 30 seconds at that level.

Why does my overload relay trip when a large fan starts?

The relay's trip class is likely too low for the load. A Class 10 relay trips at 10 seconds, but a high-inertia fan may draw locked-rotor current for 12 or 15 seconds, so the relay sees sustained 600% current and assumes the motor is burning up. Moving to a Class 30 relay gives the motor time to get past the acceleration phase.

Should I set the overload relay dial to FLA or breaker size?

Set the dial to the motor's nameplate FLA. The circuit breaker is sized for contactor inrush current and wiring fault capacity, while the overload relay is sized to the motor's continuous thermal limit. Even with a 1.15 service factor, the relay should generally stay at base FLA, because FLA x 1.15 uses up the thermal buffer and leaves no margin for voltage imbalances.

Can a thermal overload relay protect against single-phasing?

A basic bimetallic relay measures current, not winding temperature, so it often trips only after localized hotspots have exceeded the insulation's limit. With one phase lost, current in the remaining two phases can jump to 150% to 200% of normal. Electronic overloads monitor each phase individually and trip in milliseconds if one phase drops to zero.