Koyo DirectLOGIC PLC Part Numbers Decoded
A Koyo DirectLOGIC number starts with the family, then gives the number of points, then the signal type. D0-06DD1 is a DL06 PLC with DC inputs and sinking DC outputs. D2-09BDC2-1 is a 9-slot DL205 base that runs on 125 VDC. F0-04DAH-1 is a 4-channel current output module for a DL05 or DL06. One wrong character can mean the wrong supply voltage or the wrong output type. We read every number below on its own DirectLOGIC or Terminator product page on November 29, 2026.
What does the start of the number mean?
| Starts with | Family | Example |
|---|---|---|
| D0-05, D0-06 | DL05 and DL06 small PLCs | D0-05DR, D0-06DD1 |
| D0 or F0 (other) | Option modules for DL05 and DL06 | D0-08TR, F0-04THM |
| D2, F2, H2 | DL205 modular PLC | D2-09B-1, F2-08TR, H2-ERM100 |
| D3, F3 | DL305 modular PLC | D3-16ND2F, F3-16ND3F |
| D4, F4, H4 | DL405 modular PLC | D4-16TA, F4-CP128-1, H4-CTRIO |
| T1K, T1H | Terminator field I/O | T1K-08TA, T1H-EBC100 |
The number after the letter is the family, so a D2 module does not fit a D4 base.
How do you read a DL05 or DL06 PLC number?
After D0-05 or D0-06, the first letter is the input and the second is the output. A DL05 has 8 inputs and 6 outputs. A DL06 has 20 inputs and 16 outputs.
| Number | Inputs | Outputs | Power |
|---|---|---|---|
| D0-05AR, D0-06AR | AC | Relay | AC |
| D0-05DR, D0-06DR | DC | Relay | AC |
| D0-05AA, D0-06AA | AC | Triac | AC |
| D0-05DA, D0-06DA | DC | Triac | AC |
| D0-05DD, D0-06DD1 | DC | Sinking | AC |
| D0-06DD2 | DC | Sourcing | AC |
| D0-05DR-D, D0-06DR-D | DC | Relay | 12-24 VDC |
| D0-05DD-D, D0-06DD1-D | DC | Sinking | 12-24 VDC |
| D0-06DD2-D | DC | Sourcing | 12-24 VDC |
Two traps here. The D at the end, after the dash, is about power: D0-06DD1 runs on AC and D0-06DD1-D runs on 12-24 VDC. And the 1 or 2 is about the output: DD1 sinks, DD2 sources. If that difference is new to you, read NPN vs PNP sensor wiring, which covers the same idea on the input side.
What do ND3, NA, TD1, TA and TR mean?
On the I/O modules, the digits give the points and the letters give the signal:
| Letters | Signal | Example |
|---|---|---|
| NA | AC input | D4-16NA: 16 points, 120 VAC |
| ND2 | DC input, sourcing | D4-64ND2: 64 points, 24 VDC |
| ND3 | DC input, sinking or sourcing | D2-08ND3: 8 points, 12-24 VDC |
| TA | AC output | D4-08TA: 8 points, 24-240 VAC |
| TD1 | DC output, sinking | D4-16TD1: 16 points, 5-24 VDC |
| TD2 | DC output, sourcing | D4-16TD2: 16 points, 12-24 VDC |
| TR | Relay output | D2-08TR: 8 relays |
Do not guess the voltage from the letters. D4-08NA takes 120-240 VAC, but D4-16NA takes 120 VAC. Do not guess the current either: D4-08TA is 2 A per point and D4-16TA is 0.5 A per point. Our PLC I/O signal types page explains each kind.
Which power does a D2 base need?
The answer is in the letters after the slot count.
| Number | Slots | Power the base needs |
|---|---|---|
| D2-03B-1, D2-04B-1, D2-06B-1, D2-09B-1 | 3, 4, 6, 9 | 110-220 VAC |
| D2-04BDC1-1, D2-06BDC1-1 | 4, 6 | 12-24 VDC |
| D2-06BDC2-1, D2-09BDC2-1 | 6, 9 | 125 VDC |
So BDC1 and BDC2 are not interchangeable. A D2-06BDC1-1 is a low-voltage base and a D2-06BDC2-1 needs 125 VDC. The AC bases are listed with a 24 VDC, 300 mA auxiliary output. The DC base pages do not list one, so check whether anything in the panel uses that output before you change base type.
How do you read the analog modules?
On the F0 analog modules, the number counts the channels and the ending gives the signal: -1 is current and -2 is voltage.
- AD is input: F0-04AD-1 is 4 channels, current, 12-bit. F0-08ADH-2 is 8 channels, voltage, 16-bit.
- DA is output: F0-04DAH-1 is 4 channels, current, 16-bit. F0-08DAH-2 is 8 channels, voltage, 16-bit.
- AD and DA together is a combo: F0-4AD2DA-2 has 4 voltage inputs and 2 voltage outputs.
- RTD and THM are temperature inputs: F0-04RTD for RTDs, F0-04THM for thermocouples.
On the current and voltage pages we read, the F0 modules with an H are 16-bit, and the F0-04AD modules without it are 12-bit. Treat that as a pattern to check, not a rule.
Why does an 8-point Terminator module need a 16-size base?
Terminator modules plug into a separate terminal base, and the S versions need the bigger one. T1K-08TA has 8 outputs in two groups of 4 and uses a T1K-08B or T1K-08B-1 base. T1K-08TAS also has 8 outputs, but each one is isolated, and it needs a T1K-16B or T1K-16B-1 base. T1K-08TR and T1K-08TRS follow the same pattern. The -1 on a base means spring clamps instead of screws. See remote I/O vs centralised I/O for where this kind of hardware fits.
Which DirectLOGIC parts are retired?
These pages show a retired date or a notice, and most name a suggested replacement:
| Number | Status on the page | Suggested replacement |
|---|---|---|
| D2-230 | Retired 06/2017 | D2-250-1 (now retired too) |
| D2-240 | Retired 04/2017 | D2-250-1 (now retired too) |
| D2-250-1 | Retired 12/2021 | D2-262 |
| D2-260 | Retired 06/2021 | D2-262 |
| D4-440 | Retired 10/2018 | D4-454 |
| D4-450 | Retired 02/2018 | D4-454 |
| H2-EBC | Retired 03/2011 | H2-EBC100 (direct replacement) |
| D3-16ND2F | Retired 01/2015 | F3-16ND3F (listed as sinking or sourcing) |
| D0-05AA | To be discontinued | D0-05AR |
| D0-05DA, D0-05AD | To be discontinued | None |
Read the replacement line with care. D0-05AA has triac outputs and D0-05AR has relay outputs, so the suggested part does not switch the load in the same way. For a CPU, save the program from the old unit while it still runs, and test it before you change over. Our guide on what to do when a PLC module is discontinued has the full checklist, and PLC lifecycle status by maker compares how brands label old parts.
Questions people ask about DirectLOGIC numbers
Can I use a D0-06DD2 in place of a D0-06DD1?
Not without changing the wiring. One sources and the other sinks. Match the number, or have a qualified person review the output circuit.
Can I use F0-04DAH-2 in place of F0-04DAH-1?
No. The -1 gives a current signal and the -2 gives a voltage signal. The device at the other end must match.
What is D2-CTRINT?
It is a DL205 pulse module with 4 high-speed inputs and 2 high-speed sinking outputs, rated 5 kHz.
Does the dash and last digit matter?
Yes. On a base, -1 is part of the full number. On an analog module it sets current or voltage. Copy the whole number from the label.
Further reading on this site: NPN vs PNP sensor wiring; PLC I/O signal types; remote I/O vs centralised I/O; what to do when a PLC module is discontinued; PLC lifecycle status by maker; Koyo parts; request a quote.
Panel work is for a qualified person, with the supply locked out. Need a module? Browse Koyo parts or request a quote with the full number from the label.