Beckhoff EL3312 — EtherCAT Terminals

Brand: Beckhoff SKU: EL3312 Mfr Part #: EL3312
Ships Same Day* Worldwide Shipping

The EL3312 analog input terminal allows thermocouples to be connected directly. The EtherCAT Terminal's circuit can operate thermocouple sensors using the 2-wire technology. Linearization over the full temperature range is realized with the aid of a

Approvals/markings CE, CCC, UL, ATEX, IECEx
Connection technology 2-wire
Conversion time approx. 1.2 s up to 7 ms, depending on configuration and filter setting, default: approx. 125 ms
Current consumption E-bus 200 mA
Current consumption power contacts
Distributed clocks
Electrical isolation 500 V (E-bus/signal voltage)
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Ex marking ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc
Input filter cut-off frequency typ. 1 kHz
Measurement uncertainty (temperature measurement) at 23°C ambient temperature, with internal cold junction, according type: B: ±8.5°C; C: ±6.2°C; E: ±2.5°C; J: ±2.7°C; K: ±3°C; L: ±2.3°C; N: ±3°C; R: ±6.7°C; S: ±7.1°C; T: ±2.9°C; U: ±2.5°C; for further details see documentation
Measurement uncertainty (voltage measurement) at ±75 mV, 23°C ambient temperature: < ±0.14% (relative to full scale value)
Number of inputs 2
Operating Temperature -25…+60°C
Power Supply via the E-bus
Protect. rating/installation pos. IP20/variable
Relative Humidity 95%, no condensation
Resolution 16 bit, representation adjustable: 0.1/0.01°C or 1/2/4 µV per digit
Special Features channel by channel wire break detection, internal and external cold junction, firmware filter adjustable
Storage Temperature -40…+85°C
Temperature measurement (thermocouple) type B, C, E, J, K, L, N, R, S, T, U (default setting: type K)
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Voltage measurement ±30/±60/±75 mV
Weight approx. 60 g

Frequently Asked Questions

How do I get pricing for EL3312?

KKM Solutions is a quote-based industrial supplier, so prices are not listed online. Send the quote form on this page with your quantity, or email orderdesk@kkmsolutions.com, and our order desk will reply with pricing and availability within 1 business day.

Who manufactures the EL3312?

EL3312 is a Beckhoff part. KKM Solutions sources Beckhoff components to the exact manufacturer specification and cross-checks every order against manufacturer part data before it ships.

What are the key specifications of EL3312?

Key specifications include Approvals/markings: CE, CCC, UL, ATEX, IECEx; Connection technology: 2-wire; Conversion time: approx. 1.2 s up to 7 ms, depending on configuration and filter setting, default: approx. 125 ms; Current consumption E-bus: 200 mA. The full specification table on this page lists every published attribute for this part.

How quickly can EL3312 ship?

In-stock items are dispatched the same business day for orders placed by 3 PM; sourced and quoted items ship per the quoted lead time. KKM Solutions ships worldwide — to your site, warehouse, or freight forwarder.

Related Products