Allen-Bradley Solid-State Temperature Sensor 837T-D3N12A50PA-D4

Brand: Allen-Bradley SKU: 837T-D3N12A50PA-D4
Ships Same Day* Worldwide Shipping

Allen-Bradley 837T-D3N12A50PA-D4 - industrial components - Output: IO-link™ - Version 1.1 (Pin 4). With the IO-link option, switching output OUT 1 is always PNP; Storage Temperature: -20 °C; Operating pressure: 150 bar (2175 psi) maximum, with high temperature model (compression fitting is included) 50 bar (725 psi) at 120 °C (248 °F).

The Allen-Bradley 837T-D3N12A50PA-D4 is part of the industrial components range in our industrial catalog. The manufacturer's published data for this part number specifies Output: IO-link™ - Version 1.1 (Pin 4). With the IO-link option, switching output OUT 1 is always PNP and Storage Temperature: -20 °C.

Key manufacturer data on file for this item includes Operating pressure: 150 bar (2175 psi) maximum, with high temperature model (compression fitting is included) 50 bar (725 psi) at 120 °C (248 °F); Ambient temperature: -20 °C; Housing material: Stainless Steel 304; Lifecycle Status: Active; Build America, Buy America: No; Repair Options Available: No; Shock: 50 G (1.76 oz) (IEC 60068-2-27, mechanical); Vibration: Probe Length ≤150 mm (5.91 in): 6 G (0.21 oz) (IEC 60068-2-6, under resonance), Probe Length ≥250 mm (9.84 in): 2 G (0.07 oz) (IEC 60068-2-6, under resonance); Connection type: 4 pin DC micro (M12); Application: Measurement and monitoring of set temperatures; Display: ≤ ±0.8% of span ± temperature sensor error ±1 digit; Humidity: 45...75 % r. h.. The complete technical table is shown in the Specifications tab on this page.

Adjustment accuracy switching points ≤ ±0.5% of span
Ambient temperature -20 °C
Analog signal ≤ ±0.5% of span ± temperature sensor error
Analogue output 4 mA ... 20 mA true
Application Measurement and monitoring of set temperatures
Atmospheric pressure 950 mbar
Build America, Buy America No
Connection type 4 pin DC micro (M12)
Current consumption Switching outputs with: analog signal 4...20mA @ 70mA, without analog signal: 45 mA
Diameter measuring insert 6 mm
Display ≤ ±0.8% of span ± temperature sensor error ±1 digit
Display head material Personal computer + ABS-blend
Display type Display/push button
Display window material Polycarbonate
Element measurement Pt1000, 2-wire, DIN EN 60751/Class A
Housing material Stainless Steel 304
Humidity 45...75 % r. h.
Ingress rating IP65 and IP67. The stated ingress protection (per IEC 60529) only applies when plugged in with mating connectors that have the appropriate ingress protection
Insulation voltage 500V DC
Keyboard material TPE-E
Length measuring insert 50 mm
Lifecycle Status Active
Load Analog signal 4...20 mA: ≤0.5 kΩ
Nominal position Process connection lower mount (LM)
Operating pressure 150 bar (2175 psi) maximum, with high temperature model (compression fitting is included) 50 bar (725 psi) at 120 °C (248 °F)
Output IO-link™ - Version 1.1 (Pin 4). With the IO-link option, switching output OUT 1 is always PNP
Output mode Selectable - normally open, normally closed, window, hysteresis
Output threshold OUT 1 and OUT 2 are individually adjustable
Output Voltage Power supply -1 V
Overvoltage protection 40V DC
Power Supply 24V DC
Process Connection 1/4 NPT male
Rated output current OUT 1 maximum 100 mA, OUT 2 maximum 250 mA
Repair Options Available No
Response time T05 <5 s (per DIN EN 60751), T09 <10 s (per DIN EN 60751)
Reverse polarity protection V+ vs. V-
Scaling analog signal 0...25% of span, Full scale: 75...100% of span
Service life 100000000 switching cycles
Shock 50 G (1.76 oz) (IEC 60068-2-27, mechanical)
Short circuit protection 4...20 mA, out 1/out 2 vs. V-
Storage Temperature -20 °C
Switching output ≤ ±0.8% of span ± temperature sensor error
Temperature error (0.15 + 0.002 (t - 32)/1.8) for fahrenheit
Temperature measuring range -20 °C
Temperature range 15 to 25 °C (59-77 °F)
Temperature sensor material Stainless Steel 316Ti
Vibration Probe Length ≤150 mm (5.91 in): 6 G (0.21 oz) (IEC 60068-2-6, under resonance), Probe Length ≥250 mm (9.84 in): 2 G (0.07 oz) (IEC 60068-2-6, under resonance)
Zero offset adjustment Maximum 3% of span

Frequently Asked Questions

How do I get pricing for 837T-D3N12A50PA-D4?

KKM Solutions is a quote-based industrial supplier, so prices are not listed online. Send the quote form on this page with your quantity, or email orderdesk@kkmsolutions.com, and our order desk will reply with pricing and availability within 1 business day.

Who manufactures the 837T-D3N12A50PA-D4?

837T-D3N12A50PA-D4 is a Allen-Bradley part. KKM Solutions sources Allen-Bradley components to the exact manufacturer specification and cross-checks every order against manufacturer part data before it ships.

What are the key specifications of 837T-D3N12A50PA-D4?

Key specifications include Adjustment accuracy switching points: ≤ ±0.5% of span; Ambient temperature: -20 °C; Analog signal: ≤ ±0.5% of span ± temperature sensor error; Analogue output 4 mA ... 20 mA: true. The full specification table on this page lists every published attribute for this part.

How quickly can 837T-D3N12A50PA-D4 ship?

In-stock items are dispatched the same business day for orders placed by 3 PM; sourced and quoted items ship per the quoted lead time. KKM Solutions ships worldwide — to your site, warehouse, or freight forwarder.

Related Products