Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5 Hp 20A 20AD011C3AYNACC0
| AC input overvoltage trip | 570V AC @ 480V |
|---|---|
| AC input undervoltage trip | 280V AC @ 480V |
| Acceleration/deceleration | Two independently progmable accel and decel times. Each time can be progmed from 0...3600 s in 0.1 s increments |
| Altitude | 1000 m (3300 ft.) maximum without derating |
| Application in domestic- and commercial area permitted | true |
| Application in industrial area permitted | true |
| Atmosphere | Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust, If the drive is not going to be installed immediately, store the drive where it is not exposed to a corrosive atmosphere |
| Brake IGBT | Brake IGBT installed |
| Brake Resistor | Without drive mounted brake resistor |
| Build America, Buy America | No |
| Bus overvoltage trip | 810V DC @ 480V |
| Bus undervoltage fault level | 300V DC @ 480V |
| Bus undervoltage output shutoff | 437V DC @ 480V |
| Bus voltage, nom | 648V DC @ 480V |
| Carrier frequency | Standard control: 2, 3, 4, 5, 6, 7, 8, 9, and 10 kHz, vector control: 2, 4, 8, and 12 kHz, drive rating based on 4 kHz |
| Circuit breaker current rating, max | 40A @ 480V AC, 3-phase |
| Control | Enhanced Control with 24V I/O |
| Control logic noise immunity | Showering arc transients upto 1500V peak |
| Control method | Sine coded PWM with progmable carrier frequency. Ratings apply to all drives |
| Control options | Enhanced control with 24V I/O |
| Cooling fan operation | Frames B, D, and E: fan operates when power is applied and in run condition |
| Current limit capability | Proactive current limit progmable from 20...160% of rated output current, Independently progmable proportional and integral gain |
| Degree of protection (IP) | IP66 |
| Degree of protection (NEMA) | 4X |
| Depth, approx | IP20, NEMA/UL Type 1: 179.8 mm |
| Displacement power factor (all drives) | 0.98 across speed range |
| Documentation | Manual |
| Drive overcurrent trip | Software current limit: 20...160% of rated current |
| Drive to motor power ratio, max | Recommended not greater than 2:1 ratio |
| Drive to motor power ratio, min | Recommended not less than 1:2 ratio |
| Dual element time delay fuse current rating | 15...20A @ 480V AC, 3-phase |
| Efficiency | 97.5% at rated A, nominal line volts |
| Enclosure Type | Wall/machine mount-IP66/NEMA Type 4X/12 (indoor use) |
| Encoder duty cycle | 50% ±10% |
| Encoder quadrature | 90° ±27° |
| Encoder supply | 5V/12V configurable ±5% |
| Encoder Type | Incremental, dual channel |
| External watts loss | 140.0 W @ 480V @ 7.5Hp normal duty |
| Feedback option | No ftdback |
| Feedback Options | No ftdback |
| Filter Options | W/ EMC Filt & ComModeChoke |
| Frequency accuracy | Digital input: within ±0.01% of set output frequency |
| Frequency control-speed regulation | With slip compensation (Volts per Hz mode): 0.5% of base speed across 40:1 speed range, 40:1 operating range, 10 rad/sec bandwidth |
| Ground fault trip | Phase-to-ground on drive output |
| Heat sink thermistor | Monitored by microprocessor overtemp trip |
| Height, approx | IP20, NEMA/UL Type 1: 300 mm |
| Human interface model | LCD display, full numeric keypad |
| Input current rating | 9.5A @ 480V AC, 1-phase |
| Input frequency tolerance | 47 Hz |
| Input phases | Three-phase input provides full rating for all drives. single-phase ops provides 50% of rated current |
| Input power rating | 7.9 kVA @ 480V AC, 3-phase |
| Integrated breaking resistance | false |
| Intermittent overload | 110% overload capability for up to 1 min, 150% overload capability for up to 3 s |
| Internal Communication Module | ControlNet coaxial |
| Internal dynamic brake resistors | 115 ohm |
| Internal EMC filtering | s environment filter per CE EMC directive (89/336/EEC) |
| Internal watts loss | 27.8 W @ 480V @ 7.5Hp normal duty |
| Lifecycle Status | End_of_life |
| Line transients | Up to 6000 volts peak per IEEE C62.41-1991 |
| Logic control ride-thru | 0.5 s minimum, 2 s typical |
| Mains frequency | 50 Hz |
| Mains voltage | 480 V |
| Motor circuit protector current rating, max | 15A @ 480V AC, 3-phase |
| Motor overload protection | Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272 |
| Non-time delay fuse current rating | 15...40A @ 480V AC, 3-phase |
| Number of analogue inputs | 2 |
| Number of analogue outputs | 1 |
| Number of digital inputs | 6 |
| Number of digital outputs | 2 |
| Number of HW-interfaces RS-232 | 2 |
| Number of HW-interfaces RS-485 | 2 |
| Number of HW-interfaces USB | 2 |
| Number of phases input | 3 |
| Number of phases output | 3 |
| Output current rating | 11 A, 7.5 Hp normal duty, 5 Hp heavy duty, frame C |
| Output current rating, 1 min | 6.1A @ 480V AC, 1-phase |
| Output current rating, 3 sec | 8.3A @ 480V AC, 1-phase |
| Output current rating, continuous | 5.5A @ 480V AC, 1-phase |
| Output frequency range | Standard control: 0...400 Hz, enhanced control: 0...500 Hz |
| Output voltage range | 0 to rated motor voltage |
| Pollution degree 1 according to EN 61800-5-1 | No pollution occurs, only dry non-conductive pollution occurs, and has no influence |
| Pollution degree 2 according to EN 61800-5-1 | Normally only non-conductive pollution occurs, Occasionally a temporary conductivity, caused by condensation is expected when the drive is out of ops |
| Pollution degree 3 according to EN 61800-5-1 | Conductive pollution occurs, dry non-conductive pollution occurs and becomes conductive due to condensation |
| Pollution degree 4 according to EN 61800-5-1 | The pollution generates persistent conductivity caused, for exAle, by conductive dust, rain or snow |
| Power ride-thru | 15 ms at full load |
| Relative Humidity | 5...95% noncondensing |
| Relative symmetric net voltage tolerance | 10 % |
| Repair Options Available | Yes |
| Selectable motor control | Sensorless vector with full tuning. Standards V/Hz with full custom capability and vector control |
| Shock | 15 G peak for 11 ms duration (±1.0 ms) |
| Short circuit current rating, max | Maximum short circuit current rating to match specified fuse/circuit breaker capability |
| Short circuit rating, max | 200000 A symmetrical |
| Short circuit trip | Phase-to-phase on drive output |
| Speed control-speed regulation | Without ftdback (Vector Control mode): 0.1% of base speed across 120:1 speed range, 120:1 operating range, 30 rad/sec bandwidth |
| Stop modes | Multiple progmable stop modes including - RA, Coast, DC-brake, Fast brake, RA-to-hold and S-curve |
| Storage Temperature | -40 °C |
| Sub Brand | PowerFlex 70 AC Drive |
| Supporting protocol for CAN | true |
| Supporting protocol for DeviceNet | true |
| Supporting protocol for EtherNet/IP | true |
| Supporting protocol for Modbus | true |
| Supporting protocol for PROFIBUS | true |
| Supporting protocol for TCP/IP | true |
| Surrounding air temperature, max | IP66, NEMA/UL Type 4X/12(indoor): 0...40 °C (32...104 °F) without derating |
| Surrounding environment pollution degree | All enclosures are acceptable for pollution degree 1 and 2, an enclosure that meets or exceeds IP54, NEMA/UL type 12, is required for pollution degree 3 and 4 |
| Torque regulation | Without ftdback +/-10%, with ftdback +/-5% |
| Total watts loss | 167.8 W @ 480V @ 7.5Hp normal duty |
| Vibration | 0.152 mm (0.006 in) displacement, 1 G peak |
| Voltage tolerance | -10 % |
| Weight, approx | IP20, NEMA/UL Type 1: 6.89 kg |
| Width, approx | IP20, NEMA/UL Type 1: 185 mm |
| With control element | true |
Frequently Asked Questions
How do I get pricing for 20AD011C3AYNACC0?
KKM Solutions is a quote-based industrial supplier, so prices are not listed online. Send the quote form on this page with your quantity, or email orderdesk@kkmsolutions.com, and our order desk will reply with pricing and availability within 1 business day.
Who manufactures the 20AD011C3AYNACC0?
20AD011C3AYNACC0 is a Allen-Bradley part. KKM Solutions sources Allen-Bradley components to the exact manufacturer specification and cross-checks every order against manufacturer part data before it ships.
What are the key specifications of 20AD011C3AYNACC0?
Key specifications include AC input overvoltage trip: 570V AC @ 480V; AC input undervoltage trip: 280V AC @ 480V; Acceleration/deceleration: Two independently progmable accel and decel times. Each time can be progmed from 0...3600 s in 0.1 s increments; Altitude: 1000 m (3300 ft.) maximum without derating. The full specification table on this page lists every published attribute for this part.
How quickly can 20AD011C3AYNACC0 ship?
In-stock items are dispatched the same business day for orders placed by 3 PM; sourced and quoted items ship per the quoted lead time. KKM Solutions ships worldwide — to your site, warehouse, or freight forwarder.
Related Products
Allen-Bradley Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5…
Allen-Bradley Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5…
Allen-Bradley Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5…
Allen-Bradley Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5…
Allen-Bradley Allen-Bradley PowerFlex 70 AC Drive 11 A at 7.5…
Allen-Bradley
Industrial & MRO Parts