3WA1220-6.E66-.... withdrawable circuit breaker, with guide frame, IEC 60947-2, size 2, 3-pole, In=2000 A up to 690 V A
withdrawable circuit breaker, with guide frame, IEC 60947-2, size 2, 3-pole, In=2000 A up to 690 V AC 50/60 Hz, breaking capacity C Icu=130/100 kA at 500/690 V, ETU600 LSI electronic trip unit upgradeable, color display, Bluetooth, USB interface, basic protection LT, ST, INST, neutral conductor prot
withdrawable circuit breaker, with guide frame, IEC 60947-2, size 2, 3-pole, In=2000 A up to 690 V AC 50/60 Hz, breaking capacity C Icu=130/100 kA at 500/690 V, ETU600 LSI electronic trip unit upgradeable, color display, Bluetooth, USB interface, basic protection LT, ST, INST, neutral conductor protection requires an external neutral point current sensor, trip alarm switch (1x CO), connection at rear, horizontal at top, vertical at bottom guide frame with shutter and position signaling switch,
| Category | 3WA1220 |
|---|