3WA1220-6.C85-.... withdrawable circuit breaker, with guide frame, IEC 60947-2, size 1, 4-pole, N pole on right, In=200
withdrawable circuit breaker, with guide frame, IEC 60947-2, size 1, 4-pole, N pole on right, In=2000 A up to 690 V AC 50/60 Hz, breaking capacity C Icu=130/100 kA at 500/690 V, ETU300 LSI G electronic trip unit optimized for standard applications, without display, basic protection LT, ST, INST, GF,
withdrawable circuit breaker, with guide frame, IEC 60947-2, size 1, 4-pole, N pole on right, In=2000 A up to 690 V AC 50/60 Hz, breaking capacity C Icu=130/100 kA at 500/690 V, ETU300 LSI G electronic trip unit optimized for standard applications, without display, basic protection LT, ST, INST, GF, including protection of the N conductor (internal neutral point sensor available), trip alarm switch (1x CO), connection at rear, vertical at top, horizontal at bottom guide frame with shutter and position signaling switch,
| Category | 3WA1220 |
|---|